Description
This powerpoint presentation begins by providing a brief overview of electrolysis and water treatment, Oxidation-Reduction Potential (ORP) and disinfection, the effect ORP has on bacteria, changing ORP without addingoxidizing or reducing agents, and the MIOX Bench-TopElectrolysis Unit. Several experiments are presented, including: Experiment 1,MIOX Bench-TopElectrolysis Unit – 1; Experiment 2,Batch Electrolysis Unit; Experiment 3,Flow Through Electrolysis Unit; Experiment 3a&b,HPC Growth vs. Applied Current; and, Experiment 3c,HPC Growth vs. Dechlorinating Agent. Conclusions were that: it is possible to adjust the ORP of natural and syntheticwater by using Electrolysis;although some chemical changes result, by themselvesthey do not impact bacterial growth;there is a strong decrease in bacterial growth causedby changing the ORP of water; and,the different dechlorinating agents do not impactbacterial growth differently. Includes tables, figures.
Product Details
- Edition:
- Vol. – No.
- Published:
- 11/01/2007
- Number of Pages:
- 39
- File Size:
- 1 file , 920 KB
- Note:
- This product is unavailable in Ukraine, Russia, Belarus